Fault clearing at current zero ​

Open in simulator →

A bolted three-phase-to-ground fault is fed through a 230 kV line, and a breaker clears it about five cycles later with each pole opening at its own current zero.

A 230 kV source feeds a line modelled as 5 Ω and 0.1 H per phase. A bolted three-phase-to-ground fault at the far end starts at t=20 ms and is never removed. The breaker is commanded open at t=100 ms; with its interrupting current set to zero, each pole waits for its own current zero before it opens.

The line's reactance at 60 Hz is 37.7 Ω, so the symmetrical fault current is 132.8 kV/|5+j37.7| Ω=3.5 kA rms, or 4.9 kA peak. The fault starts at an arbitrary point on the wave, so each phase also carries a DC offset that decays with the line's L/R=20 ms time constant. That is why the first peaks reach up to 7.2 kA.

An AC breaker cannot interrupt a large current mid-wave: the arc keeps conducting until the current passes through zero. This sample models that directly. The breaker's interrupt_current is 0, so after the open command at 100 ms each pole stays closed until its current changes sign. Phase b clears first, at 101.1 ms, then phase a at 103.9 ms and phase c at 106.6 ms. The zeros are a sixth of a cycle (2.8 ms) apart because the source neutral and the fault are both grounded, so each phase behaves as an independent circuit. After the last pole opens, the fault current is below 1 mA, the current the breaker's 1 GΩ off resistance lets through.

The plot shows the fault currents ifa, ifb, ifc in kA and the breaker pole states brk_a, brk_b, brk_c.

Things to try ​

  • Open instantly. Set interrupt_current back to its large default. All three poles open at 100 ms on the same step, chopping each current wherever it happens to be. With this purely series circuit the current simply stops, but any parallel capacitance or a second inductive branch would now see a large transient recovery voltage.
  • Change the fault type. An isolated three-phase fault (ABC) has no path to ground, so the first pole to clear leaves the other two in series. They then clear together, a quarter-cycle later: phase b at 101.1 ms, then a and c at 105.2 ms.
  • Raise the X/R ratio. Drop the line resistance to 1 Ω. The DC offset now decays over 100 ms instead of 20 ms, so it is still large when the breaker opens. It shifts each phase's current zeros: the poles now clear at 102.2, 103.8 and 105.8 ms.

The run is 200 ms at a 20 µs step.