Skip to content

Line energization overvoltage ​

Open in simulator →

A breaker closes a 230 kV source onto an unloaded, open-ended transmission line, and the travelling wave doubles at the far end.

An ideal 230 kV, 60 Hz source closes onto a three-phase Bergeron line (Z1=300 Ω, τ1=1 ms; Z0=500 Ω, τ0=1.3 ms) at t=12.5 ms. The receiving end is open apart from a 10 MΩ measurement resistor, so the arriving wave reflects with coefficient +1 and the receiving-end voltage vr jumps to twice the arriving wave.

Closing a breaker launches a voltage wave down the line equal to the source voltage at the instant of closing. When it reaches the open far end, the reflection coefficient is +1. The reflected wave adds to the incident one and the receiving-end voltage jumps to twice the incident value. The reflection then travels back to the source, which, being ideal, reflects it with coefficient −1, and the line rings at its quarter-wave frequency, 1/(4τ1)=250 Hz, on top of the 60 Hz steady state.

With 1 pu taken as the phase peak, 2302/3=187.8 kV, the worst phase reaches 2.15 pu and the other two 1.88 and 1.91 pu. The phases differ only because each one closes at a different point on its own wave. The source is balanced and all three poles close together, so the phase voltages always sum to zero and the zero-sequence mode (Z0, τ0) is never excited. The source is ideal and the line is lossless, so the ringing does not decay over the 50 ms run.

The plot shows the receiving-end phase voltages vr_a, vr_b, vr_c and the sending-end voltages vs_a, vs_b, vs_c just past the breaker. Before the close both are zero.

Things to try ​

  • Move the closing instant. The breaker's trigger_times sets it. Closing near a voltage zero of one phase cuts that phase's overvoltage; closing at its peak maximises it. Controlled switching, closing each pole at its own voltage zero, is how utilities keep energization overvoltages down.
  • Add source impedance. Switch the source to R-L with some inductance. The source no longer reflects with −1, the steady state rises slightly with the line's charging current (the Ferranti effect), and the peaks change.
  • Lengthen the line. Double τ1 and τ0: the ringing frequency halves and the open-end steady-state voltage rises.

The run is 50 ms at a 10 µs step.

In the course ​