Line energization overvoltage
A breaker closes a 230 kV source onto an unloaded, open-ended transmission line, and the travelling wave doubles at the far end.
Closing a breaker launches a voltage wave down the line equal to the source voltage at the instant of closing. When it reaches the open far end, the reflection coefficient is +1. The reflected wave adds to the incident one and the receiving-end voltage jumps to twice the incident value. The reflection then travels back to the source, which, being ideal, reflects it with coefficient −1, and the line rings at its quarter-wave frequency,
With 1 pu taken as the phase peak,
The plot shows the receiving-end phase voltages vr_a, vr_b, vr_c and the sending-end voltages vs_a, vs_b, vs_c just past the breaker. Before the close both are zero.
Things to try
- Move the closing instant. The breaker's
trigger_timessets it. Closing near a voltage zero of one phase cuts that phase's overvoltage; closing at its peak maximises it. Controlled switching, closing each pole at its own voltage zero, is how utilities keep energization overvoltages down. - Add source impedance. Switch the source to
R-Lwith some inductance. The source no longer reflects with −1, the steady state rises slightly with the line's charging current (the Ferranti effect), and the peaks change. - Lengthen the line. Double
and : the ringing frequency halves and the open-end steady-state voltage rises.
The run is 50 ms at a 10 µs step.