3-Phase PQ Meter
Three-phase active / reactive power meter using instantaneous power theory — no fundamental-frequency parameter is needed. Takes the three phase voltages (Va, Vb, Vc) and currents (Ia, Ib, Ic) as control signals and computes total three-phase active power P = Va·Ia + Vb·Ib + Vc·Ic and instantaneous reactive power Q = [(Vb−Vc)·Ia + (Vc−Va)·Ib + (Va−Vb)·Ic] / √3. Both outputs are smoothed by a first-order low-pass filter 1/(τs+1); for a BALANCED sinusoidal set P and Q are already constant so τ mainly matters for unbalanced or distorted inputs. P and Q are three-phase totals (3× the per-phase value for a balanced system). Set τ = 0 for the raw instantaneous values.
Category: Continuous
Ports
| Port | Kind | Signal | Notes |
|---|---|---|---|
va | Control input | Real | |
vb | Control input | Real | |
vc | Control input | Real | |
ia | Control input | Real | |
ib | Control input | Real | |
ic | Control input | Real | |
p | Control output | Real | |
q | Control output | Real |
Parameters
| Parameter | Type | Default | Units | Description | ID |
|---|---|---|---|---|---|
| τ (s) | Number | 0.0167 | — | Time constant of the first-order low-pass filter applied to both P and Q (1/(τs+1)). For balanced inputs the instantaneous P and Q are already ripple-free, so this mainly smooths unbalanced / harmonic-laden inputs. Set τ = 0 to output the raw instantaneous values with no filtering. | time_constant |