Transmission Line Type ​

The data a Transmission Line uses: single- or three-phase, PI or Bergeron, entered as surge impedance, per-length RLC, sequence data or a balanced matrix, plus a default length. Types are stored with the circuit and edited from the Line types panel, not placed on the canvas; every Transmission Line that references a type follows its edits.

Category: Transmission

Ports ​

This component has no wired ports.

Parameters ​

Config ​

ParameterTypeDefaultUnitsDescriptionID
ConductorsChoice: 1 / 31—Number of conductors. 1 = single-phase (one electrical node per terminal); 3 = three-phase (one electrical_3ph node per terminal). More counts are future work.number_of_conductors
Data entryChoice: Bergeron — Surge Impedance / Bergeron — RLC / PI — RLC / Physical (coming soon)Bergeron — Surge Impedance—How the single-phase line is parameterized. Bergeron entries give a travelling-wave model; PI gives a lumped nominal-pi section. All forms reduce to the same canonical R/L/C.data_entry_1ph
Data entryChoice: Bergeron — Sequence Surge Impedance / Bergeron — Sequence RLC / Bergeron — Balanced Matrix / PI — Sequence RLC / PI — Balanced Matrix / Physical (coming soon)Bergeron — Sequence Surge Impedance—How the three-phase line is parameterized. Sequence / matrix data is reduced to positive- and zero-sequence canonical R/L/C.data_entry_3ph
Length (km)Number100—Default line length in km. Per-length data is multiplied by it; a placed Transmission Line can override it.length

Bergeron Parameters ​

ParameterTypeDefaultUnitsDescriptionID
Zc (Ω)Number400—Surge / characteristic impedance.zc
τ (travel time)Number100µs (also s, ms)One-way travel time of the line.tau

RLC Parameters ​

ParameterTypeDefaultUnitsDescriptionID
RNumber0.05Ω/km (also Ω/m, pu/km)Series resistance per unit length. Choose pu/km to enter book per-unit data (e.g. Kundur r); the value is converted with Z_base = V_base² / S_base from the Units tab.r_per_len
LNumber0.000001H/m (also H/km, mH/km, µH/km, pu/km)Series inductance per unit length (default 1e-6 H/m = 1 mH/km). With pu/km the value is read as series reactance per km (book xL) in per-unit: L = x·Z_base / (2π·Freq).l_per_len
CNumber1e-11F/m (also F/km, mF/km, µF/km, pu/km)Shunt capacitance per unit length (default 1e-11 F/m = 0.01 µF/km). With pu/km the value is read as shunt susceptance per km (book bc) in per-unit: C = b / (Z_base·2π·Freq).c_per_len

Sequence Surge Impedance ​

ParameterTypeDefaultUnitsDescriptionID
Z1 (Ω)Number350—Positive-sequence surge impedance.z1
τ1 (travel time)Number100µs (also s, ms)Positive-sequence one-way travel time.tau1
Z0 (Ω)Number550—Zero-sequence surge impedance.z0
τ0 (travel time)Number130µs (also s, ms)Zero-sequence one-way travel time.tau0

Sequence RLC ​

ParameterTypeDefaultUnitsDescriptionID
R1Number0.03Ω/km (also Ω/m, pu/km)Positive-sequence series resistance per unit length. Choose pu/km to enter book per-unit data (e.g. Kundur r); converted with Z_base = V_base² / S_base from the Units tab.r1_per_len
L1Number9e-7H/m (also H/km, mH/km, µH/km, pu/km)Positive-sequence series inductance per unit length (default 9e-7 H/m = 0.9 mH/km). With pu/km the value is read as positive-sequence series reactance per km (book xL) in per-unit: L1 = x·Z_base / (2π·Freq).l1_per_len
C1Number1.2e-11F/m (also F/km, mF/km, µF/km, pu/km)Positive-sequence shunt capacitance per unit length (default 1.2e-11 F/m = 0.012 µF/km). With pu/km the value is read as positive-sequence shunt susceptance per km (book bc) in per-unit: C1 = b / (Z_base·2π·Freq).c1_per_len
R0Number0.3Ω/km (also Ω/m, pu/km)Zero-sequence series resistance per unit length. Choose pu/km to enter book per-unit data; converted with Z_base = V_base² / S_base from the Units tab.r0_per_len
L0Number0.0000026H/m (also H/km, mH/km, µH/km, pu/km)Zero-sequence series inductance per unit length (default 2.6e-6 H/m = 2.6 mH/km). With pu/km the value is read as zero-sequence series reactance per km in per-unit: L0 = x·Z_base / (2π·Freq).l0_per_len
C0Number8e-12F/m (also F/km, mF/km, µF/km, pu/km)Zero-sequence shunt capacitance per unit length (default 8e-12 F/m = 0.008 µF/km). With pu/km the value is read as zero-sequence shunt susceptance per km in per-unit: C0 = b / (Z_base·2π·Freq).c0_per_len

Balanced Matrix ​

ParameterTypeDefaultUnitsDescriptionID
Rs (Ω)Number3—Total per-phase series resistance (self) at the type's default length. A placed line that overrides the length scales it in proportion.rs_ohm
LsNumber0.0000015H/m (also H/km, mH/km, µH/km)Self inductance per unit length (diagonal of L matrix; default 1.5e-6 H/m = 1.5 mH/km).ls_per_len
LmNumber5.7e-7H/m (also H/km, mH/km, µH/km)Mutual inductance per unit length (off-diagonal of L matrix; default 5.7e-7 H/m = 0.57 mH/km). L1 = Ls − Lm, L0 = Ls + 2·Lm.lm_per_len
CsNumber1.1e-11F/m (also F/km, mF/km, µF/km)Self capacitance per unit length (diagonal of Maxwell C matrix; default 1.1e-11 F/m = 0.011 µF/km).cs_per_len
CmNumber1e-12F/m (also F/km, mF/km, µF/km)Mutual capacitance per unit length (magnitude of off-diagonal; default 1e-12 F/m = 0.001 µF/km). C1 = Cs + Cm, C0 = Cs − 2·Cm.cm_per_len

Units ​

ParameterTypeDefaultUnitsDescriptionID
S_base (MVA)Number100—System base apparent power in MVA. Used by `pu` impedance / admittance conversions in this component's `computations` block.S_base
V_base (kV)Number230—Base RMS line-to-line voltage in kV. Used by `pu` impedance / admittance conversions in this component's `computations` block.V_base
Frequency (Hz)Number60—Frequency in Hz. Used by `B` (susceptance) / `X` (reactance) conversions in this component's `computations` block.Freq