Fault (1-phase)
Single-phase fault block. Inserts a configurable fault resistance between two electrical nodes for a timed window or under external trigger control. Use for short-circuit and ground-fault studies.
Category: Single-Phase / Sources
Ports
| Port | Kind | Signal | Notes |
|---|---|---|---|
N1 | Electrical terminal | — | |
N2 | Electrical terminal | — | |
enable | Control input | Integer | Shown when Trigger mode is Control input |
Parameters
Config
| Parameter | Type | Default | Units | Description | ID |
|---|---|---|---|---|---|
| R fault | Number | 0.01 | — | Fault path resistance between N1 and N2 when active (Ω). Typical: 0.001 - 0.1 (bolted), 1 - 50 (arcing). | fault_resistance |
| Trigger mode | Choice: Timed window / Control input | Timed window | — | `timed` = active in [t_trigger, t_clear]. `control` = follows the integer `enable` input (≠0 = active; drive it from a flag block such as Relational Double or Relational Int, or through a Double → Int converter). After deactivation, branch waits for |i| < `i_threshold` before opening (current-zero clearing). | trigger_mode |
| t trigger (s) | Number | 0.05 | — | Fault activation time (s) for `timed` mode. | t_trigger |
| t clear (s) | Number | 0.15 | — | Clear-command time (s) for `timed` mode. Branch then waits for |i| < `i_threshold` before opening (avoids di/dt spike under load). | t_clear |
| I clear threshold (A) | Number | 1 | — | |i| below which the branch may open after deactivation. Larger = clears earlier; smaller = waits closer to natural zero. 0 = true current-zero clearing (may delay up to one cycle). | i_threshold |
| Measure fault current | Choice: Off / On | Off | — | Emit the fault current (A) flowing from N1 into the fault. | measure_current |
| Positive direction | Choice: +ve in / +ve out | +ve in | — | Sign convention for this current. '+ve in' (default) is positive when current flows into the fault from N1. '+ve out' flips the sign. | current_dir |
Current Monitoring
| Parameter | Type | Default | Units | Description | ID |
|---|---|---|---|---|---|
| Fault current name | Text | If | — | current_name |
Observables
| Default name | Kind | Recorded when | Description | ID |
|---|---|---|---|---|
| set by Fault current name | Signal | Measure fault current is on | Fault current flowing from N1 into the fault (A). Positive into the fault from N1 for '+ve in' (default); the other direction flips the sign. | i_fault |