RLC Branch (3-phase) ​

Three-phase series-RLC branch — single component carrying both an EMT trapezoidal R+L+C Norton companion and a load-flow R/X row. Per-phase impedance is series R + jωL + 1/(jωC). Enter each of R, L and C in its own unit, chosen from the dropdown (Ω / kΩ / pu / Siemens for R; H / mH / pu / X reactance / X.pu for L; F / µF / pu / B susceptance / B.pu for C); the pu / reactance / susceptance options read the bases from the Units tab. Set any element to 0 to remove it — the element is shorted out, drawn as a plain wire, and the icon tag shrinks to the elements that remain (e.g. RL when C = 0). Use for short overhead lines, series-compensated lines, transformer-leakage equivalents, or any branch whose per-phase impedance is approximately series-R + L (+ optional series-C). For long cables with significant charging current, use the Transmission Line component (PI / Bergeron).

Category: Three-Phase / Passive

Ports ​

PortKindSignalNotes
iThree-phase terminal—
jThree-phase terminal—

Parameters ​

Config ​

ParameterTypeDefaultUnitsDescriptionID
RNumber0.5Ω (also kΩ, pu, S)Per-phase series resistance. Pick a unit from the dropdown; pu / Siemens conversions read the bases from the Units tab. Drives the EMT Norton companion and the load-flow R column (R_pu = R / Z_base on the from-bus side). Enter 0 to remove the resistor (shorted out — drawn as a plain wire).r_ohms
LNumber0.01H (also mH, pu, Ω, X.pu)Per-phase series inductance. Pick a unit from the dropdown; pu / X (Ω reactance) / X.pu conversions read the bases from the Units tab. Drives EMT and the inductive part of load-flow X (X_L_pu = ωL / Z_base). Enter 0 to remove the inductor (shorted out — drawn as a plain wire).l_henries
CNumber0F (also μF, pu, S, B.pu)Per-phase series capacitance. Pick a unit from the dropdown; pu / B (Siemens susceptance) / B.pu conversions read the bases from the Units tab. Capacitive part of load-flow X (X_C_pu = −1/(ωC·Z_base); series-comp convention). Total X = X_L + X_C. Default 0 = no capacitor (pure series-RL). Enter 0 to remove the capacitor (shorted out — drawn as a plain wire).c_farads
Measure currentChoice: Off / OnOff—Emit per-phase branch currents (positive = `i` → `j`). Signal names are on this row; blank skips a phase.measure_current
Positive directionChoice: +ve in / +ve out+ve in—Sign convention for this current. '+ve in' (default) is positive when current flows into port i, toward j, on every phase. '+ve out' flips the sign.current_dir

Current Monitoring ​

ParameterTypeDefaultUnitsDescriptionID
Current name ATextIa—Signal name for Phase A branch current. Blank skips this phase.i_name_a
Current name BTextIb—Signal name for Phase B branch current.i_name_b
Current name CTextIc—Signal name for Phase C branch current.i_name_c

Units ​

ParameterTypeDefaultUnitsDescriptionID
S_base (MVA)Number100—System base apparent power in MVA. Used by `pu` impedance / admittance conversions in this component's `computations` block.S_base
V_base (kV)Number230—Base RMS line-to-line voltage in kV. Used by `pu` impedance / admittance conversions in this component's `computations` block.V_base
Frequency (Hz)Number60—Frequency in Hz. Used by `B` (susceptance) / `X` (reactance) conversions in this component's `computations` block.Freq

Observables ​

Default nameKindRecorded whenDescriptionID
set by Current name ASignalMeasure current is onPhase A series-branch current (A). Positive = current flowing from `i` to `j`. The direction switch keeps this sign by default and flips it the other way.branchCurrent_a
set by Current name BSignalMeasure current is onPhase B series-branch current (A). Positive into port i, toward j, on every phase for '+ve in' (default); the other direction flips the sign.branchCurrent_b
set by Current name CSignalMeasure current is onPhase C series-branch current (A). Positive into port i, toward j, on every phase for '+ve in' (default); the other direction flips the sign.branchCurrent_c

Used in samples ​