Appearance
Transmission Line
A transmission line between end A and end B. Its data (PI or Bergeron, single- or three-phase, R/L/C or surge impedance) comes from a Transmission Line Type stored with the circuit; the line itself only sets an optional length override and per-end current monitoring. Use Split line to draw end B as a separate Transmission Line End, for example in another subsystem; splitting changes only the drawing, not the simulation.
Category: Transmission
Ports
| Port | Kind | Signal | Notes |
|---|---|---|---|
end_a | Electrical terminal | — | Shown when Conductors is 1 |
end_a3 | Three-phase terminal | — | Shown when Conductors is 3 |
end_b | Electrical terminal | — | Shown when Conductors is 1 and Split is Joined |
end_b3 | Three-phase terminal | — | Shown when Conductors is 3 and Split is Joined |
Parameters
Config
| Parameter | Type | Default | Units | Description | ID |
|---|---|---|---|---|---|
| Line name | Text | (empty) | — | Unique name of this line in the circuit. It names the line's observables and its far end. Filled in automatically when the line is placed. | line_name |
| Line type | Text | (empty) | — | The Transmission Line Type this line uses (its R/L/C or surge-impedance data, PI or Bergeron, and conductor count). Pick one of the circuit's types or create a new one. | line_type |
| Override length | Choice: Off / On | Off | — | When On, this line uses its own length instead of the type's default length. Only available for types entered per unit length. | length_override |
| Length (km) | Number | 100 | — | This line's length in km, used instead of the type's default length. | length |
| Monitor end A current | Choice: Off / On | Off | — | When On, end A of the line publishes the current at its pin as an observable. Each end is monitored independently. | a_measure_current |
| End A positive current direction | Choice: Into Line / Out of Line | Into Line | — | Sign convention for end A's monitored current. 'Into Line' = positive when current flows from the network into the line at this end; 'Out of Line' = positive when it flows out of the line into the network. | a_current_dir |
| Monitor end B current | Choice: Off / On | Off | — | When On, end B of the line publishes the current at its pin as an observable. Each end is monitored independently. | b_measure_current |
| End B positive current direction | Choice: Into Line / Out of Line | Into Line | — | Sign convention for end B's monitored current. 'Into Line' = positive when current flows from the network into the line at this end; 'Out of Line' = positive when it flows out of the line into the network. | b_current_dir |
End A Current Monitoring
| Parameter | Type | Default | Units | Description | ID |
|---|---|---|---|---|---|
| End A current name | Text | (empty) | A (also kA) | Signal name for end A's current. Leave blank to auto-name it after the line. Single-phase only. Pick a unit; the published value is scaled to it. | a_current_name |
| End A phase A current name | Text | (empty) | A (also kA) | Signal name for phase A current at end A. Leave blank to skip phase A. Pick a unit; the published value is scaled to it. | a_current_name_pa |
| End A phase B current name | Text | (empty) | A (also kA) | Signal name for phase B current at end A. Leave blank to skip phase B. Pick a unit; the published value is scaled to it. | a_current_name_pb |
| End A phase C current name | Text | (empty) | A (also kA) | Signal name for phase C current at end A. Leave blank to skip phase C. Pick a unit; the published value is scaled to it. | a_current_name_pc |
End B Current Monitoring
| Parameter | Type | Default | Units | Description | ID |
|---|---|---|---|---|---|
| End B current name | Text | (empty) | A (also kA) | Signal name for end B's current. Leave blank to auto-name it after the line. Single-phase only. Pick a unit; the published value is scaled to it. | b_current_name |
| End B phase A current name | Text | (empty) | A (also kA) | Signal name for phase A current at end B. Leave blank to skip phase A. Pick a unit; the published value is scaled to it. | b_current_name_pa |
| End B phase B current name | Text | (empty) | A (also kA) | Signal name for phase B current at end B. Leave blank to skip phase B. Pick a unit; the published value is scaled to it. | b_current_name_pb |
| End B phase C current name | Text | (empty) | A (also kA) | Signal name for phase C current at end B. Leave blank to skip phase C. Pick a unit; the published value is scaled to it. | b_current_name_pc |