Transmission Line
Synthetic two-port transmission line assembled from a placed Transmission Line (and its far end, when split) and the line type it references. Not placed directly — the netlist converter creates one per placed line. Implements PI (lumped nominal-pi) and Bergeron (travelling-wave) models in single-phase and three-phase forms.
Category: Transmission
Ports
| Port | Kind | Signal | Notes |
|---|---|---|---|
end_a | Electrical terminal | — | Shown when Conductors is 1 |
end_b | Electrical terminal | — | Shown when Conductors is 1 |
end_a3 | Three-phase terminal | — | Shown when Conductors is 3 |
end_b3 | Three-phase terminal | — | Shown when Conductors is 3 |
Parameters
| Parameter | Type | Default | Units | Description | ID |
|---|---|---|---|---|---|
| Conductors | Choice: 1 / 3 | 1 | — | 1 = single-phase (ports end_a/end_b), 3 = three-phase (ports end_a3/end_b3). | number_of_conductors |
| Model | Choice: PI / Bergeron | Bergeron | — | PI = lumped nominal-pi section. Bergeron = travelling-wave. Set by the converter; the converter falls back to PI when the travel time is shorter than the time step. | model |
| R (Ω) | Number | 1 | — | Single-phase total series resistance (canonical). | R |
| L (H) | Number | 0.1 | — | Single-phase total series inductance (canonical). | L |
| C (F) | Number | 0.000001 | — | Single-phase total shunt capacitance (canonical). | C |
| R1 (Ω) | Number | 3 | — | Positive-sequence total series resistance (canonical, 3-phase). | R1 |
| L1 (H) | Number | 0.09 | — | Positive-sequence total series inductance (canonical, 3-phase). | L1 |
| C1 (F) | Number | 0.0000012 | — | Positive-sequence total shunt capacitance (canonical, 3-phase). | C1 |
| R0 (Ω) | Number | 30 | — | Zero-sequence total series resistance (canonical, 3-phase). | R0 |
| L0 (H) | Number | 0.26 | — | Zero-sequence total series inductance (canonical, 3-phase). | L0 |
| C0 (F) | Number | 8e-7 | — | Zero-sequence total shunt capacitance (canonical, 3-phase). | C0 |
Observables
| Default name | Kind | Recorded when | Description | ID |
|---|---|---|---|---|
| set by End-A current name | Signal | Emit 1ph current (end A) is on | Single-phase current at terminal end_a, scaled to the chosen unit (A / kA): series-branch current plus the end_a shunt-charging current. Positive 'out of end_a into the line' unless the end-A terminal selects '+ve in'. | branchCurrent |
| set by End-A phase A current name | Signal | Emit 3ph current (end A) is on | Phase A current at terminal end_a, scaled to the chosen unit (A / kA). | branchCurrent_a |
| set by End-A phase B current name | Signal | Emit 3ph current (end A) is on | Phase B current at terminal end_a, scaled to the chosen unit (A / kA). | branchCurrent_b |
| set by End-A phase C current name | Signal | Emit 3ph current (end A) is on | Phase C current at terminal end_a, scaled to the chosen unit (A / kA). | branchCurrent_c |
| set by End-B current name | Signal | Emit 1ph current (end B) is on | Single-phase current at terminal end_b, scaled to the chosen unit (A / kA): series-branch current plus the end_b shunt-charging current. Positive 'out of end_b into the line' unless the end-B terminal selects '+ve in'. | branchCurrentB |
| set by End-B phase A current name | Signal | Emit 3ph current (end B) is on | Phase A current at terminal end_b, scaled to the chosen unit (A / kA). | branchCurrentB_a |
| set by End-B phase B current name | Signal | Emit 3ph current (end B) is on | Phase B current at terminal end_b, scaled to the chosen unit (A / kA). | branchCurrentB_b |
| set by End-B phase C current name | Signal | Emit 3ph current (end B) is on | Phase C current at terminal end_b, scaled to the chosen unit (A / kA). | branchCurrentB_c |