PQ Load (3-phase) ​

Three-phase static load carrying both an EMT voltage-dependent model AND a load-flow PL/QL row. The load_type selects how the drawn P and Q vary with the terminal voltage V around the nominal V_nom: Constant Power (P,Q held), Constant Current (P,Q ∝ V), Constant Impedance (P,Q ∝ V²), or ZIP (a polynomial blend P = P₀·[Zp·u² + Ip·u + Pp], u = V/V_nom, six independent fractions for P and Q). The EMT side is modelled as a per-phase parallel conductance G(V) and inductance L(V) to ground; the per-step terminal RMS voltage is tracked over a 1/f window and the non-impedance terms are re-injected as a Norton correction each step. A low-voltage cutoff reverts the constant-power / constant-current terms to constant-impedance below v_cutoff_pu so the draw stays finite during faults. The load-flow side stays a textbook constant-power PL/QL model; the two converge exactly when the solved bus voltage equals v_nom_v. Optional per-phase current monitoring and a low-pass-filtered P/Q monitor (Akagi instantaneous power, user-selectable units) publish observables. An optional in-line breaker (a ganged 3-pole switch) can disconnect the load from the bus, driven either by a list of toggle times or by a named command signal; its initial state is drawn on the canvas.

Category: Three-Phase / Passive

Ports ​

PortKindSignalNotes
busThree-phase terminal—

Parameters ​

Config ​

ParameterTypeDefaultUnitsDescriptionID
PNumber10MW (also W, kW)3-phase real-power demand at V_nom. Pick a unit from the dropdown (stored canonically in watts). Drives the load-flow PL column and the EMT model's nominal real draw. Positive = drawn from the bus.p_w
QNumber3MVAr (also VAr, kVAr)3-phase reactive-power demand at V_nom. Pick a unit from the dropdown (stored canonically in vars). Positive = inductive (L > 0); negative = capacitive (v1 EMT collapses |Q| to inductive with a warning). Drives QL and the EMT susceptance.q_var
V nom (LL)Number13800V (also kV, pu)Line-to-line RMS voltage at which (P, Q) are specified. Pick a unit from the dropdown (stored canonically in volts); pu multiplies by V_base from the Units tab. The EMT voltage-dependence ratio is u = |V| / V_nom; EMT and PF match exactly when |V| = V_nom.v_nom_v
f ratedNumber60—System frequency (Hz). Sizes the equivalent inductance (L = X / 2πf) and the 1/f window used to track the terminal RMS voltage for the voltage-dependence.f_rated_hz
Load typeChoice: Constant Power (P) / Constant Current (I) / Constant Impedance (Z) / ZIPConstant Impedance (Z)—How the drawn P and Q vary with terminal voltage V (u = V/V_nom). Constant Power: P,Q held flat (∝ u⁰). Constant Current: P,Q ∝ u. Constant Impedance: P,Q ∝ u² (fixed admittance — the legacy model). ZIP: polynomial blend P₀·[Zp·u² + Ip·u + Pp] with six independent Z/I/P fractions on the ZIP tab.load_type
Low-V cutoff (pu)Number0.7—Below this voltage (per-unit on V_nom) the constant-power and constant-current terms revert to constant impedance so the current draw stays finite during deep sags / faults (I ∝ 1/V would otherwise diverge as V→0). Constant-impedance loads ignore this. Typical 0.6–0.8.v_cutoff_pu
Measure currentChoice: Off / OnOff—Emit per-phase load currents (positive = into the load) as observables. Signal names are on this row; blank skips a phase.measure_current
Positive directionChoice: +ve in / +ve out+ve in—Sign convention for this current. '+ve in' (default) is positive when current flows into the load from the bus, on every phase. '+ve out' flips the sign.current_dir
Monitor P/QChoice: Off / OnOff—Emit measured real (P) and reactive (Q) power drawn by the load as observables. Uses the instantaneous Akagi form, low-pass filtered with the time constant on the Power Monitoring tab to reject 2ω ripple. Names and units on the Power Monitoring tab.monitor_pq
BreakerChoice: None / Time Triggered / Signal TriggeredNone—Optional in-line breaker between the bus terminal and the load (a ganged 3-pole switch — all three phases open/close together). None: the load is permanently connected. Time Triggered: the breaker toggles open↔closed at each time listed on the Breaker tab. Signal Triggered: a named signal commands the breaker (> 0 = closed, ≤ 0 = open). While the breaker is open the load is disconnected from the bus (draws ~0 current); load-flow P/Q is unaffected by the breaker.breaker
Initial stateChoice: Open / ClosedClosed—Breaker state at t = 0, and the symbol drawn on the canvas (Closed = arm bridges the contacts, load connected; Open = arm lifted, load disconnected). For Time Triggered this is the state before the first trigger time; for Signal Triggered it holds for the first step until the command signal is read.breaker_initial_state

Breaker ​

ParameterTypeDefaultUnitsDescriptionID
Trigger time(s)Text(empty)—Comma-separated trigger times in seconds, e.g. `2` or `2,4,6`. The breaker toggles state (open↔closed) at each time, starting from the Initial state. Blank = never toggles (the breaker stays at the Initial state for the whole run).breaker_times
Trigger signalText(empty)—Name of a published signal that commands the breaker: > 0 = closed, ≤ 0 = open. Resolved by name the same way as a GoTo output, a labelled wire, or another component's observable, and read 1-step delayed. Blank holds the breaker at the Initial state.breaker_signal_name
Breaker state nameText(empty)—Optional. Name for an observable reporting the breaker state (1 = closed, 0 = open) so it can be plotted. Blank = not published.breaker_state_name

ZIP ​

ParameterTypeDefaultUnitsDescriptionID
Zp (real, ∝V²)Number1—Constant-impedance fraction of the REAL power. The three real fractions Zp + Ip + Pp are normalised to sum to 1 internally.zp_frac
Ip (real, ∝V)Number0—Constant-current fraction of the REAL power.ip_frac
Pp (real, ∝V⁰)Number0—Constant-power fraction of the REAL power.pp_frac
Zq (react, ∝V²)Number1—Constant-impedance fraction of the REACTIVE power. The three reactive fractions Zq + Iq + Pq are normalised to sum to 1 internally.zq_frac
Iq (react, ∝V)Number0—Constant-current fraction of the REACTIVE power.iq_frac
Pq (react, ∝V⁰)Number0—Constant-power fraction of the REACTIVE power.pq_frac

Current Monitoring ​

ParameterTypeDefaultUnitsDescriptionID
Current name ATextIa—Signal name for Phase A load current.i_name_a
Current name BTextIb—Signal name for Phase B load current.i_name_b
Current name CTextIc—Signal name for Phase C load current.i_name_c

Power Monitoring ​

ParameterTypeDefaultUnitsDescriptionID
P/Q filter τ (sec)Number2—Low-pass filter time constant for the measured P and Q. Smaller tracks transients; larger gives a cleaner steady-state but slower response. Default 2 s rejects 50/60 Hz ripple strongly. Set 0 for the raw instantaneous values.pq_time_constant
P signal nameTextP—Signal name for the filtered real power P drawn by the load. Blank = skip.p_signal_name
P unitChoice: W / kW / MWMW—Unit the published P observable is scaled to.p_monitor_unit
Q signal nameTextQ—Signal name for the filtered reactive power Q drawn by the load. Blank = skip.q_signal_name
Q unitChoice: VAr / kVAr / MVArMVAr—Unit the published Q observable is scaled to.q_monitor_unit

Units ​

ParameterTypeDefaultUnitsDescriptionID
V_base (kV)Number230—Base RMS line-to-line voltage in kV. Used by `pu` impedance / admittance conversions in this component's `computations` block.V_base

Observables ​

Default nameKindRecorded whenDescriptionID
set by Current name ASignalMeasure current is onPhase A load current (A). Positive = current drawn from the bus into the load. The direction switch keeps this sign by default and flips it the other way.branchCurrent_a
set by Current name BSignalMeasure current is onPhase B load current (A). Positive into the load from the bus, on every phase for '+ve in' (default); the other direction flips the sign.branchCurrent_b
set by Current name CSignalMeasure current is onPhase C load current (A). Positive into the load from the bus, on every phase for '+ve in' (default); the other direction flips the sign.branchCurrent_c
set by P signal nameSignalMonitor P/Q is onMeasured real power P drawn by the load. Sum of instantaneous v·i across the three phases, low-pass filtered with τ = pq_time_constant, scaled to the chosen P unit (W / kW / MW).p_filtered
set by Q signal nameSignalMonitor P/Q is onMeasured reactive power Q drawn by the load. Akagi instantaneous reactive power (1/√3)·(v_bc·i_a + v_ca·i_b + v_ab·i_c), low-pass filtered with τ = pq_time_constant, scaled to the chosen Q unit (VAr / kVAr / MVAr). Positive = inductive.q_filtered
set by Breaker state nameSignalBreaker is onBreaker state: 1 = closed (load connected), 0 = open (load disconnected). Only meaningful when a breaker is enabled.breaker_state